Toshiba air conditioner error codes: what they mean and what to do


Toshiba uses two kinds of error code. Home wall units such as Seiya, Shorai Edge and Haori show two-character codes on the remote in CHECK mode, such as 04 (connecting cable or signal fault) or 1C (compressor drive), and flash their lamps; commercial Digital Inverter (RAV) and VRF systems show letter codes such as E04 (indoor-outdoor communication), P10 (water overflow) and P15 (gas leakage) on the wired remote. This guide from LE Company, air conditioning engineers in London, takes the meanings from Toshiba’s own service and installation manuals. For repairs, see our air conditioning repair in London page.
Need an engineer? LE Company repairs Toshiba air conditioning across London. Call +44 20 3603 7172, Monday to Saturday 8am to 8pm, or see air conditioning repair in London.
Every repair we do starts with checking and cleaning the system. Many of the faults behind these codes, from a frozen indoor coil to an overheated outdoor unit, come from blocked filters, a dirty coil or a blocked condensate drain, and after a proper service the code often does not come back. That is why we service first and replace parts only when a test shows the part is faulty. See what an air conditioning service covers.

Toshiba home units: reading the code and the flashing lamps

From Toshiba’s service manual: press CHECK on the back of the wireless remote and 00 appears. Press the temperature up button to step through 00, 01, 02 and on. For a code with no fault the unit beeps once; at the stored fault it beeps for 10 seconds and all its lamps flash five times a second: write that code down. Press the power button to leave. Switching the power off and on resets the unit but does not delete the stored code. Before using the remote, the lamps already tell you something: lamps flashing five times a second mean a fault (OPERATION alone, a circuit board; OPERATION and TIMER together, the connecting cable or signal), while the OPERATION lamp flashing once a second only means a power cut.
Home code
Toshiba meaning
Unit
04
Connecting cable or serial signal fault
Cable / signal
0C, 0d
Room sensor / indoor coil sensor fault
Indoor
11, 12
Indoor fan motor fault / other indoor board fault
Indoor
14, 16, 17
Inverter over-current, compressor position circuit, current detection circuit
Outdoor
18, 19, 1b
Outdoor coil sensor, discharge sensor, outdoor air sensor
Outdoor
1A
Outdoor fan or its drive
Outdoor
1C
Compressor drive output error
Outdoor
1d, 1E, 1F
Compressor will not turn; discharge above 117 °C; compressor high current
Outdoor
07, 21
Outdoor return signal lost after start; 21 with high coil temperature
Outdoor
0E, 25, 26
Gas detector sensor fault; refrigerant leak detected; gas detector end of life (models with a gas sensor)
Indoor

Toshiba commercial and VRF codes (wired remote)

RAV and VRF systems show the code and the indoor unit number on the wired remote while the unit is running. To see the log, hold SET and TEST for 4 seconds or more and step with the temperature buttons; Toshiba says not to press CL, which deletes the whole log.
Code
Toshiba meaning
Unit
E01, E03
No signal from or to the remote controller
Remote / indoor
E04
Indoor-outdoor serial communication fault
Indoor detects
E08
Duplicated indoor address
Indoor
E18
Header / follower indoor unit communication fault
Indoor
F01, F02
Indoor coil sensor open or short
Indoor
F04, F06, F08
Discharge, outdoor coil, outside air sensor open or short
Outdoor
H01, H02, H03
Compressor breakdown, compressor lock, current detection or phase loss
Outdoor
L09, L29
Indoor capacity not set; other outdoor unit problem
Indoor / outdoor
P03, P04
Discharge temperature too high; high pressure
Outdoor
P10
Indoor water overflow: drain blocked or float switch tripped
Indoor
P15
Gas leakage detected
Outdoor
P19
4-way valve problem (shows in heating)
Outdoor
P22, P26
Outdoor fan problem; inverter short-circuit protection
Outdoor

What does E04 mean on a Toshiba air conditioner?

E04 is the code people search for most. On RAV and VRF systems it is an indoor-outdoor serial communication fault: the wiring between the units, a loose terminal or one of the control boards. A home wall unit reports the same fault as 04. Switch the system off at the isolator for a few minutes; if it comes back, an engineer needs to test the wiring and boards.

What do P10 and P15 mean?

P10 is indoor water overflow: Toshiba gives a blocked drain or a tripped float switch, and the unit stops before water comes through the ceiling. Cleaning the drain tray and line is the usual fix, and part of every service. P15 is gas leakage detected: the system is short of refrigerant, so there is a leak to find and repair, which is work for an F-Gas engineer.

When to call an engineer

Toshiba’s owner manuals say to contact the dealer for any fault code. Before you call, clean the filters, check the outdoor unit is clear, and note the code, the lamp pattern and the model of both units. Anything that involves the refrigerant, such as a leak search, a pressure test or a gas top-up, is work for an F-Gas certified engineer. LE Company engineers hold F-Gas certificates. For other makes, see our guides to Daikin error codes, Mitsubishi air conditioner error codes, Fujitsu air conditioner error codes, LG air conditioner error codes, Samsung air conditioner error codes, Panasonic air conditioner error codes and Hitachi air conditioner error codes.

Book a Toshiba air conditioning repair in London

LE Company’s call-out is from £175 + VAT and includes the first 30 minutes on site, when the engineer reads the stored fault codes and finds the cause. The cost of the repair is agreed with you before any work starts. We fit only original parts, covered by the warranty of the company that supplies them. See our air conditioning repair in London, commercial air conditioning repair and emergency air conditioning repair pages, read our frequently asked questions, or call +44 20 3603 7172, Monday to Saturday, 8am to 8pm.

Book an engineer