Fujitsu air conditioner error codes: what they mean and what to do
A Fujitsu air conditioner reports a fault by flashing lamps on the indoor unit, and the number of flashes is a two-digit code: the green OPERATION lamp gives the first digit, the orange TIMER lamp the second, and the ECONOMY lamp flashes fast to show it is a fault. Code 11, for example, is a communication error between the indoor and outdoor units, 53 a drain pump error and A1 a discharge temperature error. This guide from LE Company, air conditioning engineers in London, takes the meanings from Fujitsu General’s own UK installation and operation manuals and explains what you can check and when to call an engineer. For repairs, see our Fujitsu air conditioner repair page.
Every repair we do starts with checking and cleaning the system. Many of the faults behind these codes, from a frozen indoor coil to an overheated outdoor unit, come from blocked filters, a dirty coil or a blocked condensate drain, and after a proper service the code often does not come back. That is why we service first and replace parts only when a test shows the part is faulty. See what an air conditioning service covers.
How to read a Fujitsu error code from the flashing lights
Each flash is half a second on and half a second off. Count the OPERATION (green) flashes for the first digit and the TIMER (orange) flashes for the second, while the ECONOMY lamp flashes fast. A second digit shown as A means 10 flashes and U means 15, so A1 is 10 flashes then 1, and 5U is 5 then 15. Let the pattern repeat at least twice. The code shows only while the unit is trying to run. Fujitsu warns that its code table covers many models, so some codes in it do not apply to yours.
To recall the last stored code on a wall unit, Fujitsu’s procedure is: stop the unit, switch the power off and back on, then within about 2 minutes press the recessed TEST RUN button on the wireless remote, or hold the MANUAL AUTO button on the indoor unit for 10 seconds or more. Count the flashes, then press ON/OFF to leave test run. Older wired remotes show E:EE; hold the two SET TEMP buttons together for 5 seconds to see the unit number and code. Touch wired remotes show the code under Status, Error Information.
Fujitsu error codes
Meanings from Fujitsu General’s UK installation manuals for wall, duct and cassette units (the ASYG, ARXG and AUXG ranges). Fujitsu’s instruction for every code is to contact authorised service personnel.
Code | Fujitsu meaning | Flashes (OPERATION / TIMER) |
11 | Serial communication error (indoor to outdoor) | 1 / 1 |
12 | Wired remote controller communication error | 1 / 2 |
14 | Network communication error | 1 / 4 |
15 | Check run unfinished / automatic airflow adjustment error | 1 / 5 |
22 | Indoor unit capacity error | 2 / 2 |
23 | Combination error | 2 / 3 |
26 | Indoor unit address setting error | 2 / 6 |
29 | Connection unit number error in wired remote system | 2 / 9 |
32 | Indoor PCB model information (EEPROM) error | 3 / 2 |
41 | Room temperature sensor error | 4 / 1 |
42 | Indoor heat exchanger middle temperature sensor error | 4 / 2 |
51 | Indoor fan motor error | 5 / 1 |
53 | Drain pump error | 5 / 3 |
5U | Indoor unit error | 5 / 15 |
62 | Outdoor main PCB model information or communication error | 6 / 2 |
63 | Inverter error | 6 / 3 |
64 | Active filter / PFC circuit error | 6 / 4 |
65 | Trip terminal L error / IPM temperature error | 6 / 5 |
71 | Discharge temperature sensor error | 7 / 1 |
72 | Compressor temperature sensor error | 7 / 2 |
73 | Outdoor heat exchanger liquid temperature sensor error | 7 / 3 |
74 | Outdoor temperature sensor error | 7 / 4 |
75 | Suction gas temperature sensor error | 7 / 5 |
77 | Heat sink temperature sensor error | 7 / 7 |
84 | Current sensor error | 8 / 4 |
86 | Pressure sensor / high pressure switch error | 8 / 6 |
94 | Trip detection | 9 / 4 |
95 | Compressor rotor position detection error (permanent stop) | 9 / 5 |
97 | Outdoor fan motor error | 9 / 7 |
99 | 4-way valve error | 9 / 9 |
A1 | Discharge temperature error | 10 / 1 |
A3 | Compressor temperature error | 10 / 3 |
A4 | High pressure error | 10 / 4 |
AC | Heat sink temperature error | 10 / 12 |
J2 | Branch box error (flexible multi-split) | 13 / 2 |
What does Fujitsu error code 11 or 11.1 mean?
Code 11 is a serial communication error: the indoor and outdoor units have stopped talking to each other. Some Fujitsu wired controllers and VRF systems add a sub-code after a dot: 11.1 is a reverse transmission error at start-up, 11.2 a reverse transmission error during operation, and 11.3 and 11.4 forward transmission errors at start-up and during operation. Fujitsu lists the interconnecting wiring, electrical noise, the outdoor main board, the outdoor fan motor and the outdoor expansion valve coil among the causes, and says not to replace parts from the code alone. Switch the system off at the isolator for a few minutes; if 11 comes back, an engineer needs to test the wiring and boards.
What does Fujitsu error code 53 mean?
53 is a drain pump error: condensate water is not being pumped away from the indoor unit, so it stops before water overflows. A drain line blocked with dirt or slime, a failed pump or a stuck float switch are the usual causes, and cleaning the tray and the line comes before any new pump. Not every leak shows a code: in one Marylebone showroom two Fujitsu ceiling units were dripping because cold air was not ducted to the grille; see air conditioner dripping water from the ceiling.
What do Fujitsu error codes A1 and A3 mean?
A1 is a discharge temperature error and A3 a compressor temperature error: the compressor is running hotter than it should. Low refrigerant after a leak, a dirty outdoor coil, an outdoor fan that is not turning and a blocked airflow around the outdoor unit are the usual causes. Clear leaves and anything stored around the outdoor unit; the rest needs an engineer. A4 is high pressure, which also often comes back to a blocked outdoor coil or fan.
Why is my Fujitsu operation light flashing?
Not every flashing lamp is a fault. In heating the lamps flash during defrost, which can last up to about 15 minutes; the filter reminder flashes, and so does a test run. It is a fault when the ECONOMY lamp flashes fast at the same time as the OPERATION and TIMER lamps. There is no Fujitsu code 1: one flash of each lamp is code 11. Codes such as JA, JC, JE or A9 are not in Fujitsu General’s manuals and usually belong to another brand, so check the make on the rating plate first.
When to call an engineer
Fujitsu’s operation manual says that if the lamps keep flashing you should stop the unit, switch off the breaker and contact service. Before you call, clean the filters, check the outdoor unit is clear and note the code, the model of the indoor and outdoor units and when the fault appears. Anything that involves the refrigerant, such as a leak search, a pressure test or a gas top-up, is work for an F-Gas certified engineer. LE Company engineers hold F-Gas certificates. For other makes, see our guides to Daikin error codes, Mitsubishi air conditioner error codes and LG air conditioner error codes.
Book a Fujitsu air conditioning repair in London
LE Company’s call-out is from £175 + VAT and includes the first 30 minutes on site, when the engineer reads the stored fault codes and finds the cause. The cost of the repair is agreed with you before any work starts. We fit only original parts, covered by the warranty of the company that supplies them. See our Fujitsu air conditioner repair, air conditioning repair in London, commercial air conditioning repair and emergency air conditioning repair pages, read our frequently asked questions, or call +44 20 3603 7172, Monday to Saturday, 8am to 8pm.