Mitsubishi air conditioner error codes: what they mean and what to do
Which Mitsubishi error code you see depends on which Mitsubishi you have. Mitsubishi Electric Mr Slim units show a letter and a digit, such as E6 (indoor/outdoor communication) or P8 (pipe temperature); wired controllers and City Multi systems show four digits, such as 2502 (drain) or 6607 (no acknowledgement); and the MSZ wall units common in UK homes show no code at all, only a blinking lamp. This guide from LE Company, air conditioning engineers in London, takes the meanings from Mitsubishi Electric’s own UK service manuals and explains what you can check and when to call an engineer. For repairs, see our Mitsubishi air conditioner repair page.
Every repair we do starts with checking and cleaning the system. Many of the faults behind these codes, from a frozen indoor coil to an overheated outdoor unit, come from blocked filters, a dirty coil or a blocked condensate drain, and after a proper service the code often does not come back. That is why we service first and replace parts only when a test shows the part is faulty. See what an air conditioning service covers.
Mitsubishi Electric or Mitsubishi Heavy Industries?
They are two different manufacturers with different codes. Mitsubishi Electric models start MSZ, MUZ and MXZ (home splits), PKA, PLA, PEA, PUZ and PUHZ (Mr Slim) or PUHY and PURY (City Multi). Mitsubishi Heavy Industries models start SRK, SRC, FDC or FDU. The model number is on the rating plate on the side of the indoor and outdoor units. If yours is Mitsubishi Heavy Industries, the codes in this guide do not apply: E36, for example, is a Mitsubishi Heavy Industries code (discharge pipe temperature) and does not exist on Mitsubishi Electric units.
Mitsubishi Electric error codes (Mr Slim)
These codes appear on a wired remote, or as beeps and blinks when you run a self-check from the wireless remote. The meanings are Mitsubishi’s wording from the PUZ-ZM and PKA service manuals.
Code | Mitsubishi meaning | Beeps on self-check |
P1 | Intake (room air) sensor error | 1 |
P2, P9 | Pipe sensor error (TH2, TH5) | 2 |
E6, E7 | Indoor/outdoor unit communication error | 3 |
P4 | Drain sensor error / float switch connector open | 4 |
P5 | Drain pump error | 5 |
P6 | Freezing / overheating protection operation | 6 |
P8 | Pipe temperature error | 8 |
E4, E5 | Remote controller signal receiving error | 9 |
Fb | Indoor unit control system error (memory error) | 12 |
E0, E3 | Remote controller transmission error | none |
E8, E9 | Indoor/outdoor communication error, outdoor unit side | 1 (outdoor pattern, E9) |
U1 | Abnormal high pressure (63H operated) | 6 (outdoor) |
U2 | High discharge or compressor temperature / insufficient refrigerant | 5 (outdoor) |
U3, U4 | Outdoor unit thermistor open or short circuit | 3 (outdoor) |
U5 | Abnormal heatsink temperature | 7 (outdoor) |
U6 | Compressor overcurrent / power module fault | 9 (outdoor) |
U8 | Outdoor unit fan protection stop | 8 (outdoor) |
Mitsubishi 4-digit error codes (wired controllers and City Multi)
PAR-30 and PAR-40 wired controllers, PUMY and City Multi systems show four digits. Be careful: the same number can mean different things on different ranges, so always give the engineer the model with the code.
Code | City Multi | Mr Slim / PUMY (2-digit code) |
1102 | Discharge temperature abnormality | Compressor temperature trouble (U2) |
1500 | Overcharged refrigerant | Superheat due to low discharge temperature (U7) |
2500 | Water leakage | Water leakage (PA) |
2502 | Drain pump abnormality | Drain overflow protection (P5) |
2503 | Drain sensor abnormality | Drain sensor abnormality (P4) |
4220 | Bus voltage drop | Voltage shortage / overvoltage (U9) |
5101 | Air inlet or discharge thermistor | Air inlet (TH21) or compressor (TH4) thermistor |
5102 | Liquid pipe thermistor (TH22) | Liquid pipe or suction pipe thermistor (U4) |
6600 | Multiple address abnormality | Duplicate address (A0) |
6602, 6603 | Transmission processor fault / bus busy | A2 / A3 |
6607 | No ACK abnormality | No ACK error (A7) |
6831, 6832 | Controller communication: no reception / synchronisation | E0/E4 and E3/E5 |
6840 | - | Indoor/outdoor communication (E6, E8) |
What does E6 mean on a Mitsubishi air conditioner?
On Mitsubishi Electric Mr Slim units, E6 (and E7) is an indoor/outdoor unit communication error; on a 4-digit wired controller the same fault shows as 6840. Mitsubishi’s own first check in the service manual is to switch the power off, wait 10 minutes and switch it on again. If E6 returns, the cause is the wiring between the indoor and outdoor units, a loose or corroded terminal, or the indoor or outdoor control board, and an engineer needs to test them before any board is replaced.
What does P8 mean on a Mitsubishi air conditioner?
P8 is a pipe temperature error: the temperature of the indoor coil is outside the range the unit expects for the mode it is in. Mitsubishi’s service manual lists refrigerant shortage, a faulty pipe thermistor or a thermistor that has come out of its holder, and a stop valve that was not fully opened among the causes. P8 is not detected in drying mode. Low refrigerant means there is a leak somewhere: topping up without finding it only delays the next call.
What do Mitsubishi error codes 2502 and P5 mean?
Water is not getting away from the indoor unit. On Mr Slim and PUMY systems 2502 is drain overflow protection, shown as P5 on the 2-digit display; on City Multi 2502 is a drain pump abnormality. A blocked drain line, a failed condensate pump or a stuck float switch all stop the unit before water comes through the ceiling. We clean the drain tray and line first, then test the pump. On one Mitsubishi system in a London home our engineers cleaned the units and fitted new condensate pumps over several visits. If water is already dripping, see our case of an air conditioner dripping water from the ceiling.
What does Mitsubishi error code 6607 mean?
6607 is a No ACK error: a unit on the control line did not acknowledge a message (A7 on the 2-digit display). It points to the transmission wiring, a unit that has lost power, or an address set wrong, not to the refrigerant circuit. Check that every indoor and outdoor unit has power and that no isolator has been switched off. 6831 and 6832 are different: they are faults between the wired controller and the indoor unit.
Why is the light blinking on my Mitsubishi wall unit?
The MSZ wall units most London homes have do not show letter codes. They report a fault by blinking the OPERATION INDICATOR lamp a number of times. If the lamp stays on for 3 seconds before the blinks, the fault is in the outdoor unit. Count the blinks over at least two cycles and give the number to the engineer, together with the model from the rating plate. A slow blink is not always a fault: check that the filters are clean and the outdoor unit is not blocked first.
How to read the stored code with the wireless remote
On Mr Slim units with a wireless remote, Mitsubishi’s service manual gives a self-check: press CHECK twice, choose the refrigerant address with the temperature buttons (usually 00), point the remote at the unit and press HOUR. The unit beeps and the lamp blinks a number of times; compare the number with the table above. Press ON/OFF to leave check mode. If you hear only the first two beeps, no fault is stored. A wired controller shows the code, the unit and the model on its screen, and Mitsubishi’s instruction is to stop the unit and consult your installer.
When to call an engineer
None of Mitsubishi’s manuals gives an owner fix for these codes. You can clean the filters, make sure nothing blocks the outdoor unit and switch the power off for 10 minutes. If the code comes back, call an engineer, and quote the code, the model of both units and when it happens (at start, after an hour, only in heating). Anything that involves the refrigerant, such as a leak search, a pressure test or a gas top-up, is work for an F-Gas certified engineer. LE Company engineers hold F-Gas certificates. Mitsubishi is the make of air conditioning our engineers see most often, from home MSZ splits to Mr Slim systems in shops and offices. For other makes, see our guides to Daikin error codes, Fujitsu air conditioner error codes and LG air conditioner error codes. If the system is still running but cools less than last year, see what our engineers found inside a Daikin air conditioner during a full strip-down service.
Book a Mitsubishi air conditioning repair in London
LE Company’s call-out is from £175 + VAT and includes the first 30 minutes on site, when the engineer reads the stored fault codes and finds the cause. The cost of the repair is agreed with you before any work starts. We fit only original parts, covered by the warranty of the company that supplies them. See our Mitsubishi air conditioner repair, air conditioning repair in London, commercial air conditioning repair and emergency air conditioning repair pages, read our frequently asked questions, or call +44 20 3603 7172, Monday to Saturday, 8am to 8pm.