Daikin error codes: what they mean and what to do
A Daikin error code is a letter and a digit, such as U4 (communication between the indoor and outdoor units), U0 (refrigerant shortage) or E7 (outdoor fan lock), and on a wall split you read it from the remote by holding the Cancel button until 00 appears. The same code can mean different things on a home wall split and on a Sky Air or VRV system, so always check which one you have. This guide from LE Company, air conditioning engineers in London, takes the meanings from Daikin’s own user reference guides, installer guides and service manuals and explains what you can check and when to call an engineer. For repairs, see our Daikin air conditioner repair page.
Every repair we do starts with checking and cleaning the system. Many of the faults behind these codes, from a frozen indoor coil to an overheated outdoor unit, come from blocked filters, a dirty coil or a blocked condensate drain, and after a proper service the code often does not come back. That is why we service first and replace parts only when a test shows the part is faulty. See what an air conditioning service covers.
How to read the error code on a Daikin remote
On a Daikin wall split with a wireless remote, Daikin’s user reference guide gives this check: point the remote at the indoor unit and hold Cancel for about 5 seconds until 00 blinks in the temperature display. Press Cancel again, one press at a time, until you hear a long continuous beep: the code on the display at that moment is the fault. A short beep or two beeps means that code is not the fault. Hold Cancel for 5 seconds to leave, or wait a minute. 00 on its own means normal. On VRV and Sky Air systems the code shows on the wired controller, often with a sub-code such as U4-01.
Daikin error codes
Meanings in Daikin’s wording. The split column is from Daikin’s FTXM, FTX and FTXS wall split documents; the Sky Air / VRV column from Daikin Europe’s VRV IV manuals and the Sky Air RZAG installer guide.
Code | Wall split (FTX, FTXM, FTXS) | Sky Air / VRV |
00 | Normal | - |
A1 | Indoor unit PCB abnormality | EEPROM failure (indoor) |
A3 | Drain level control (ducted units only) | Drain system malfunction (float switch) |
A5 | Freeze-up protection or high-pressure control | - |
A6 | Fan motor (DC motor) abnormality | Indoor fan motor malfunction / locked |
AH | - | Filter dust chamber / self-cleaning unit malfunction |
C4 | Indoor heat exchanger thermistor abnormality | Heat exchanger (liquid) thermistor malfunction |
C9 | Room temperature thermistor abnormality | Suction air thermistor malfunction |
E1 | Outdoor unit PCB abnormality | PCB malfunction (outdoor) |
E3 | High pressure switch activated | High pressure switch activated |
E5 | Compressor overload activation | Compressor lock detection |
E6 | Compressor lock | Inverter overcurrent (VRV IV+) |
E7 | DC fan lock | Outdoor fan motor malfunction |
EA | 4-way valve abnormality | - |
F3 | Discharge pipe temperature control | Discharge temperature malfunction |
F6 | High pressure control in cooling | Refrigerant overcharge detection |
H6 | Position sensor abnormality | - |
H8 | DC voltage / current sensor abnormality | - |
H9 | Outdoor temperature thermistor abnormality | Ambient temperature sensor malfunction |
J3 | Discharge pipe thermistor abnormality | Discharge temperature sensor malfunction |
J6 | Outdoor heat exchanger thermistor abnormality | De-icing temperature sensor malfunction |
L4 | Radiation fin temperature rise | Fin temperature abnormal |
L5 | Inverter instantaneous overcurrent | Inverter PCB faulty |
P4 | Radiation fin thermistor abnormality | Fin thermistor malfunction |
U0 | Refrigerant shortage | Abnormal low pressure drop, faulty expansion valve |
U2 | Over-voltage or low-voltage detection | Inverter power voltage shortage / missing phase |
U4 | Signal transmission error between indoor and outdoor unit | Faulty wiring between indoor and outdoor units |
UA | Voltage mismatch between indoor and outdoor unit | Indoor units incompatible or connection mismatch |
UH | - | Auto address malfunction |
What does U0 mean on a Daikin air conditioner?
On Daikin wall splits U0 is refrigerant shortage. On VRV systems Daikin describes it as an abnormal low pressure drop or a faulty expansion valve, and on a Sky Air test run U0 can simply mean the stop valves were never opened. So U0 is not always a gas top-up, and when it is low gas, the gas went somewhere: a leak has to be found and repaired. On one Daikin multi-split in north London, installed in 2015 and cooling poorly, our engineers found one indoor unit losing refrigerant and another frozen over; the plan was to clean the units first, then search each unit for the leak one by one.
What does U4 mean on a Daikin air conditioner?
U4 is a signal transmission error between the indoor and outdoor units: damaged or loose wiring between them, a terminal that has corroded, or a control board fault. Daikin notes that on VRV systems a U4 that appears and clears by itself a few minutes later can be electrical noise from other appliances, and that a power reset may help. A U4 that returns, or appears straight after an installation or a building works, needs an engineer to test the wiring and boards before any board is replaced.
What do Daikin error codes E5, E6 and E7 mean?
E5 is compressor overload on a split (compressor lock on VRV) and E6 compressor lock on a split. Both often come back to the compressor overheating: low refrigerant, a dirty outdoor coil or the outdoor unit boxed in so it cannot breathe. E7 is a DC fan lock, meaning the outdoor fan is not turning properly. First check that nothing blocks the fan: leaves, ice in winter, a cover left on. In one north-west London home our engineer traced a Daikin E7 to the outdoor DC fan motor. On a three-phase Sky Air unit, Daikin says E7 on the test run can also mean a missing phase.
What does A5 or A6 mean on a Daikin air conditioner?
A5 on a Daikin wall split is freeze-up protection or high-pressure control: the indoor coil is getting too cold in cooling or too hot in heating. Daikin’s own service manual lists a clogged air filter and dust on the indoor heat exchanger among the causes, which is why cleaning comes first. A6 is an indoor fan motor fault: the fan drum may be clogged with dust or the motor failing. See what we found inside two Daikin units during a full strip-down service, where the fan drums were coated with dust.
What do H6, F3 and L5 mean?
H6 is a position sensor abnormality on a split: the inverter cannot read where the compressor rotor is, which points to the compressor, its wiring or the inverter board. F3 is discharge pipe temperature control: the compressor discharge is running too hot, often from low refrigerant or a blocked outdoor coil. L5 is inverter overcurrent on a split, and an inverter board fault on VRV. All three need an engineer with test equipment.
When to call an engineer
Daikin’s own instruction is to tell your installer or service engineer the code before the error is reset, because resetting it without finding the cause only hides it. Before you call, clean the filters, check the outdoor unit is clear, note the code and the model of both units from the rating plates, and whether it happens in cooling, heating or at start-up. Anything that involves the refrigerant, such as a leak search, a pressure test or a gas top-up, is work for an F-Gas certified engineer. LE Company engineers hold F-Gas certificates. For other makes, see our guides to Mitsubishi air conditioner error codes, Fujitsu air conditioner error codes and LG air conditioner error codes, and for systems that cool one room but not another, read air conditioning not cooling one room.
Book a Daikin air conditioning repair in London
LE Company’s call-out is from £175 + VAT and includes the first 30 minutes on site, when the engineer reads the stored fault codes and finds the cause. The cost of the repair is agreed with you before any work starts. We fit only original parts, covered by the warranty of the company that supplies them. See our Daikin air conditioner repair, air conditioning repair in London, commercial air conditioning repair and emergency air conditioning repair pages, read our frequently asked questions, or call +44 20 3603 7172, Monday to Saturday, 8am to 8pm.