Hitachi air conditioner error codes: what they mean and what to do


Hitachi commercial Utopia and Set Free systems show a two-character alarm code on the wired controller, such as 01 (float switch: water in the drain pan), 03 (no communication between the indoor and outdoor units) or 53 (inverter module protection), while Hitachi wall units blink their orange timer lamp a number of times instead. This guide from LE Company, air conditioning engineers in London, takes the meanings from Hitachi’s own technical catalogue and service manuals. Hitachi’s owner manuals give no fix for any code: write down what is shown and contact a Hitachi service engineer. For repairs, see our Hitachi air conditioner repair page.
Need an engineer? LE Company repairs Hitachi air conditioning across London. Call +44 20 3603 7172, Monday to Saturday 8am to 8pm, or see Hitachi air conditioner repair.
Every repair we do starts with checking and cleaning the system. Many of the faults behind these codes, from a frozen indoor coil to an overheated outdoor unit, come from blocked filters, a dirty coil or a blocked condensate drain, and after a proper service the code often does not come back. That is why we service first and replace parts only when a test shows the part is faulty. See what an air conditioning service covers.

How Hitachi shows a fault

On Utopia and Set Free, the RUN lamp flashes and ALARM appears on the wired controller with the indoor unit address, the refrigerant cycle number, the alarm code and the model code; with several indoor units, each is shown in turn. If the RUN lamp flashes every 4 seconds, the indoor unit and the controller cannot talk to each other: a connector or the wiring. On Hitachi wall units the orange timer lamp blinks a number of times, then pauses for 2 seconds; count the blinks in one cycle. Two blinks is forced cooling, not a fault.

Hitachi Utopia and Set Free alarm codes

Code
Hitachi meaning
Unit
01
Float switch: high water in the drain pan
Indoor
02
High pressure cut or high compressor temperature
Outdoor
03
No communication between indoor and outdoor units
Communication
04
No communication between inverter board and outdoor board
Outdoor
05
Power supply phase fault
Supply
06
Abnormal inverter voltage
Outdoor
07
Discharge gas superheat too low
Refrigerant cycle
08
Discharge gas temperature too high
Refrigerant cycle
11, 12
Inlet / outlet air thermistor fault
Indoor
13, 14
Freeze protection / gas pipe thermistor fault
Indoor
19
Indoor fan protection (motor overheat or locked)
Indoor
20, 22
Compressor / outdoor air thermistor fault
Outdoor
35
Duplicate indoor unit number in the same cycle
System
47
Suction pressure too low (refrigerant shortage or leak)
Outdoor
5A
Fan controller fin temperature abnormal
Outdoor
EE
Compressor protection lockout after repeated alarms
System
Codes 31, 51, 53, 54 and 57 also appear on Hitachi systems: wrong capacity setting (31), inverter current sensor (51), inverter module protection (53), high inverter fin temperature (54) and fan controller protection (57). Hitachi’s meanings vary between generations, so check them against your model’s own manual.

What does 03 mean on a Hitachi air conditioner?

Hitachi lists the wiring between the units, loose terminals, a blown fuse and an indoor unit without power. On a system with several indoor units, check that none has been switched off at its isolator. If 03 returns with power on everywhere, an engineer needs to test the wiring and boards.

What do 01, 02, 08 and 47 mean?

01 is water in the drain pan: a blocked condensate drain or a failed drain pump, and cleaning the drain is part of every service. 02, 08 and 47 are refrigerant-side protections: high pressure, a discharge temperature too high and a suction pressure too low. Hitachi lists several causes for each, from a blocked pipe or a stuck expansion valve to too little refrigerant, so they are not simply a gas top-up. Repeated, they end in EE, a lockout only an engineer clears.

When to call an engineer

Hitachi’s instruction is to write down the indications and contact a Hitachi service engineer. Before you call, clean the filters, check the outdoor unit is clear and note the code, the unit number and the model. Anything that involves the refrigerant, such as a leak search, a pressure test or a gas top-up, is work for an F-Gas certified engineer. LE Company engineers hold F-Gas certificates. For other makes, see our guides to Daikin error codes, Mitsubishi air conditioner error codes, Fujitsu air conditioner error codes, LG air conditioner error codes, Samsung air conditioner error codes, Panasonic air conditioner error codes and Toshiba air conditioner error codes.

Book a Hitachi air conditioning repair in London

LE Company’s call-out is from £175 + VAT and includes the first 30 minutes on site, when the engineer reads the stored fault codes and finds the cause. The cost of the repair is agreed with you before any work starts. We fit only original parts, covered by the warranty of the company that supplies them. See our Hitachi air conditioner repair, air conditioning repair in London, commercial air conditioning repair and emergency air conditioning repair pages, read our frequently asked questions, or call +44 20 3603 7172, Monday to Saturday, 8am to 8pm.

Book an engineer

Leave your details and what is wrong. The bookings team will email you the call-out cost and the times an engineer can come. Call-out from £175 + VAT, including the first 30 minutes on site.