Air conditioner dripping water from the ceiling: it was cooling the ceiling, not the room
When a ceiling air conditioner drips and nobody can find a leak, check where the cold air actually goes. LE Company engineers found exactly this on two Fujitsu ceiling-mounted air conditioners in Marylebone, Central London, in 2025: the units had been installed with a gap of about 15 cm between their outlet and the ceiling grille. The cold air was cooling the ceiling void instead of the room. Where that cold air met the warm room air, at the grille, water condensed and dripped. The fix was not a part inside the unit: a short insulated duct, about 20 cm, from each unit to its grille.
We went: two Fujitsu units dripping from the ceiling
The air conditioners were concealed above the ceiling, blowing into the room through grilles in the ceiling cladding. Water was dripping at the grilles, and the cause had not been found before we were called.
We found: the cold air never reached the room
On our visit on 9 July 2025 we looked at how each unit met the ceiling. The outlet of the unit did not connect to the grille: between them was an open gap of about 15 cm. That was enough for the unit to blow its cold air into the ceiling void, so the void and the back of the grille became cold, while the room below stayed hot. The warm, humid room air met the cold grille and condensed, exactly like water on a cold glass, and the water ran off and dripped. The units themselves were working; the installation was sending their cold air to the wrong place.
We did: an insulated duct from each unit to its grille
- Recommended a duct connection for each unit and quoted the parts and labour, agreed with the customer before ordering.
- On the second visit, on 29 September 2025, fitted to each of the two units an L-shaped connector of about 20 cm from the unit outlet to the grille, insulated so it does not sweat itself, and a new grille.
- Fitted a filter box with a filter on the return-air inlet.
- Used white ducting material so the work matches the existing ceiling, in about two hours on site.
With the cold air ducted straight into the room, there is no cold void and no cold grille for room air to condense on, so the dripping stopped and the room cools as it should. The customer was happy with the result.
Air conditioner leaking water from the ceiling: what to check
Water from a ceiling air conditioner has three usual causes. A blocked condensate drain or a failed condensate pump, so the tray overflows. A drain connection that has come apart or been damaged, which we have found destroyed by paint on a Fujitsu unit in a showroom in Chelsea. Or condensation, as on this job, when cold air is not ducted properly and cools the ceiling or the grille. A drain fault leaves a wet tray and wet pipes; condensation leaves a dry drain and water on the cold surfaces. See our air conditioning repair in London page for the faults we fix, Fujitsu air conditioner repair, air conditioning service and air conditioning installation in London. Related jobs: why one room of an LG system was not cooling, another installation problem, and a full strip-down service of two Daikin units.
Questions
Why is my air conditioner dripping water from the ceiling?
Either the condensate drain is blocked or leaking, or cold air is meeting warm air and forming condensation. On two Fujitsu ceiling units in Marylebone, LE Company found the units blowing into a gap of about 15 cm above the ceiling grille, so the cold air cooled the ceiling void and water condensed at the grille.
Can condensation drip from an air con grille even if nothing is leaking?
Yes. If cold air from the unit is not ducted all the way to the grille, it cools the ceiling and the grille, and warm room air condenses on them. The water looks like a leak, but every pipe is dry.
How do you fix an air con that blows into the ceiling void?
Connect the unit outlet to the ceiling grille with a short insulated duct, so all the cold air goes into the room. On this job each unit got an L-shaped connector of about 20 cm, insulation and a new grille, and the return side got a filter box.
Who repairs ceiling air conditioning in London?
LE Company. Our F-gas certified engineers repair and service ceiling, ducted and wall-mounted air conditioning across London, on Fujitsu, Mitsubishi, Daikin, LG and other brands. Call +44 203 603 7172.
Book an air conditioning engineer
LE Company’s call-out is from £175 + VAT and includes the first 30 minutes on site. The cost of any repair is agreed with you before work starts, and we fit only original parts. Our engineers are F-gas certified. Call +44 203 603 7172, Monday to Saturday, 8am to 8pm.