LG air conditioning not cooling one room: the return air was the problem


When one room of a multi-room air conditioning system stays warm while the other rooms cool normally, the outdoor unit is usually fine and the cause is at that room: its filter, its indoor unit or the way air gets to it. LE Company engineers found exactly this in a flat in Putney, South West London, on 15 October 2026, servicing an LG Multi V S system that cools three rooms through ducted ceiling units. The living room blew 17°C air in cooling mode; the study blew 13°C. The units were working. The installation was starving the living-room unit of air.
Probe thermometer at the ceiling supply grille of an LG ducted air conditioning unit reading about 17°C in cooling mode

We went: an annual air conditioning service

The customer booked an air conditioning service for an LG system serving three rooms: a living room, a study and a bedroom, each with a ducted indoor unit hidden in the ceiling, and one LG Multi V S outdoor unit on the building’s plant level. There were no error codes on the controllers.

We found: 17°C from the living room, 13°C from the study

With every controller set to cooling at 17°C, we measured the air coming out of each supply grille with a probe thermometer. A unit like this normally delivers air at 8 to 13°C in cooling.
  • Living room: 17°C, fan on high. Too warm.
  • Study: 13.0°C, fan on high. Normal.
  • Bedroom: 15.5°C with the fan on low. Normal for a low fan.
The first question was whether the living room simply had a smaller unit. It did not: its rating plate shows an LG ARNU18GL2G4, about 5.6 kW, larger than the 3.6 kW ARNU12GL2G4 units in the study and bedroom. And because the study, on the same outdoor unit, delivered 13°C, the outdoor unit was clearly working at full capacity. All three units were tested running at the same time.
The answer was in the ceiling void. The living-room unit draws its return air from the void above the ceiling rather than from the room, through a narrow gap with little space for air to enter. A unit that cannot draw enough air cannot deliver cold air, however well it works.
Return-air side of an LG ducted air conditioning unit in a ceiling void, with little space for air to enter

We did: a full service and a clear recommendation

  • Cleaned the filter and evaporator of the living-room unit and cleared the return-air side as far as the installation allows.
  • Cleaned the filters of the study and bedroom units. Both were clean inside, with no water staining, no corrosion, no abnormal noise and dry condensate connections.
  • Cleaned the condenser coil of the outdoor unit.
Condenser coil of an LG Multi V S outdoor unit after cleaning, fins clean behind the guard grille
Our recommendation was to change the return-air arrangement of the living room so the unit can draw air properly; until then it will keep limiting the cooling in that room. We also noted a drop of condensation on the suction pipe at the outdoor unit, built in 2019, and recommended checking the temperature sensors (thermistors) and replacing them if they read out of range.

Why one room of a multi-split air con does not cool

On a multi-room or VRF system, compare the rooms before blaming the outdoor unit. If one room is warm and another on the same system is normal, look at that room: a blocked filter, a dirty evaporator, a restricted return-air path, or a fan running on low. If every room is warm, the cause is more likely shared: low refrigerant from a leak, a dirty outdoor coil or a fault in the outdoor unit. See our air conditioning repair in London page for the faults we fix, our LG air conditioner repair page, and air conditioning maintenance for planned servicing. We also service Daikin and Mitsubishi systems; read how we stripped and washed two Daikin units.

Questions

Why is one room of my air conditioning not cooling?

If other rooms on the same system cool normally, the outdoor unit is working and the cause is at that room: a blocked filter, a dirty evaporator, a restricted return-air path or a low fan speed. On an LG Multi V S in Putney, LE Company found the living-room unit drawing its return air from a cramped ceiling void.

What temperature should air con blow in cooling mode?

A unit like the LG ducted units on this job normally delivers supply air at about 8 to 13°C in cooling. Ours measured 13°C in the study and 17°C in the living room, which showed the living room had a problem.

Is it the outdoor unit if one room is warm?

Usually not. If another room on the same outdoor unit cools normally, the outdoor unit is delivering full capacity. Check the indoor unit and the airflow of the warm room first.

How often should an LG air conditioning system be serviced?

Once a year: cleaning the filters, evaporators and the outdoor condenser coil, and measuring the air temperature from every room so a problem like this is found early.

Book an air conditioning engineer

LE Company’s call-out is from £175 + VAT and includes the first 30 minutes on site. The cost of any repair is agreed with you before work starts, and we fit only original parts. Our engineers are F-gas certified. Call +44 203 603 7172, Monday to Saturday, 8am to 8pm.

Book an engineer

Leave your details and what is wrong. The bookings team will email you the call-out cost and the times an engineer can come. Call-out from £175 + VAT, including the first 30 minutes on site.